A 6U rack leaves 2U spare in the sample layout with a patch panel, cable manager, switch and gateway. Choose 9U to add the sample rack UPS and keep spare space, or 12U to keep spare space after adding a second switch, patch panel and cable manager.
Count the rack units
List the rack height of each device and accessory, then add the space you want to reserve. Use that total to shortlist a cabinet by height.
Worked example. A 1U patch panel, 1U cable manager, 1U switch and 1U gateway add up to 4U. Add a 2U UPS and the equipment fills 6U. If you want 2U of reserve as well, plan for 8U and shortlist a 9U rack.
Sample layouts for 6U, 9U and 12U
These layouts use the published heights of the Ubiquiti USW-24-POE switch and Ubiquiti UDM-Pro gateway. Each sample patch panel and cable manager is allotted 1U, and the sample UPS is allotted 2U. The positions show how the units add up.
| Cabinet | Top-to-bottom rail positions | Used | Spare |
|---|---|---|---|
| 6U | 6 patch panel, 5 cable manager, 4 switch, 3 gateway, 2–1 spare | 4U | 2U |
| 9U | 9 patch panel, 8 cable manager, 7 switch, 6 gateway, 5–3 spare, 2–1 UPS | 6U | 3U |
| 12U | 12 patch panel, 11 cable manager, 10 switch, 9 second patch panel, 8 second cable manager, 7 second switch, 6 gateway, 5–3 spare, 2–1 UPS | 9U | 3U |
Compare cabinet depth and rail support
Compare each chassis with the cabinet’s maximum device depth. For the USW-24-POE, use the published supported rack depth when checking mounting fit. Switch specs · Gateway specs
Cable clearance estimate. On each side of the mounting rails, subtract the reach of the device and its connected cables from the available cabinet depth. Measure both distances from the rails. A negative result means the device or its cables extend beyond the available space on that side.
Check wall load and access
- Add the cabinet’s empty weight and the weight of everything you’ll mount. Switch specs · Gateway specs
Evidence and limits. The listed Ubiquiti model specifications were checked on November 26, 2026. The layouts were calculated from published Ubiquiti rack heights and the sample allocations. No installation or fit testing was performed.